OT160E13CLP

Артикул: 09cd1103_OTC25-800_ryhma_720.jpg, 0505CD15_OT250E03C_720.jpg, 0505CD15_OT250E03CP_720.jpg, 0505CD07_OT250_800C_group_Level_One_720.jpg, OTM630_OTM800_2_720.jpg, OT40_125F3C_group_720.jpg
Наименование: Manual change-over switch, I - I+II - II, closed transition OT160E13CLP | 1SCA108504R1001 | OT160E13CLP
Производитель: ABB
Картинки описания: 1SCA108504R1001


General Information
Extended Product Type:
OT160E13CLP
Product ID:
1SCA108504R1001
EAN:
6417019399379
Catalog Description:
Manual change-over switch, I - I+II - II, closed transition OT160E13CLP
Long Description:
Including a black plastic IP65 I - I+II - II pistol type handle, shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking.
 
Ordering
EAN:
6417019399379
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85365080
Dimensions
Product Net Width:
205 mm
Product Net Height:
150 mm
Product Net Depth:
160 mm
Product Net Weight:
4.1 kg
Container Information
Package Level 1 Units:
1 piece
Package Level 1 Width:
170 mm
Package Level 1 Height:
185 mm
Package Level 1 Length:
270 mm
Package Level 1 Gross Weight:
4.1 kg
Package Level 1 EAN:
6417019399379
Environmental
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-01
Additional Information
Conventional Free-air Thermal Current (Ith):
q=40В°C 160 A
IIT Publishing Status:
Level 0 - Information enabled
Number of Poles:
4
Operating Mechanism:
Mechanism between the poles
Pollution Degree:
3
Position of Line Terminals:
Top in - bottom out
Power Loss:
Per Pole 2.4 W
Product Main Type:
OT160_C
Product Name:
Manual change-over switch
Rated Impulse Withstand Voltage (Uimp):
12 kV
Rated Insulation Voltage (Ui):
1000 V
Rated Operational Current AC-21A (Ie):
(380 ... 415V) 160 A
(500V) 160 A
(690V) 160 A
Rated Operational Current AC-22A (Ie):
(380 ... 415 V) 160 A
(500 V) 160 A
(690 V) 160 A
Rated Operational Current AC-23A (Ie):
(380 ... 415 V) 160 A
(500 V) 160 A
(690 V) 160 A
Rated Operational Power AC-23A (Pe):
(220 ... 240V) 45 kW
(400V) 90 kW
(415V) 90 kW
(500V) 110 kW
(690V) 160 kW
Rated Operational Voltage (Ue):
1000 V
Rated Short-time Withstand Current (Icw):
for 1.0s 8 kiloampere rms
Classifications
Object Classification Code:
Q