104-K MCS Mini Reversing Contactors, Screw Type Terminals, 5 A, System Control Voltage: 12 (7.5...15)V DC, 3 N.O. Main Contacts, 1 N.C. Auxiliary Contact || 104K05ZQ02
|
Short Circuit Ratings |
Operational Rating | Dual Element Time Delay Fuses | Circuit Breakers | Rating Reference | File Ref: UL | File Ref: CSA | Comments | ||||||||
SCCR [kA] | Max Fuse Size [A] | Fuse Class | CB Type | UL CMC Type | Catalog Numbers | SCCR [kA] | SCCR [kA] | SCCR [kA] | SCCR [kA] | |||||
600V | 480V | 480Y/277V | 600V | 600Y/347V | ||||||||||
5A (AC3/4) | 50 | 30 | CC, J | UL 508 Manual Motor Controller | -- | 140M-C2E-A16 to 140M-C2E-B16 | 65 | -- | 47 | -- | Instruction Sheet | E41850 | cULus | |
5A (AC3/4) | 50 | 30 | CC, J | UL 508 Manual Motor Controller | -- | 140M-C2E-B25 to 140M-C2E-B63 | 65 | -- | 30 | -- | Instruction Sheet | E41850 | cULus | |
5A (AC3/4) | 5 | 40 | K5, RK5 | UL 508 Type E Comb. Motor Controller | F (2 Comp) | 140M-C2E-A16 to 140M-C2E-B16 | -- | 65 | -- | 47 | Instruction Sheet | E41850 | cULus | |
5A (AC3/4) | 5 | 40 | K5, RK5 | UL 508 Type E Comb. Motor Controller | F (2 Comp) | 140M-C2E-B25 to 140M-C2E-B40 | -- | 65 | -- | 30 | Instruction Sheet | E41850 | cULus | |
5A (AC3/4) | 5 | 40 | K5, RK5 | UL 508 Type E Comb. Motor Controller | F (2 Comp) | 140M-C2E-B63 | -- | 65 | -- | -- | Instruction Sheet | E41850 | cULus | |
5A (AC3/4) | -- | -- | -- | UL 489 MCCB | -- | -- | -- | -- | -- | -- | Instruction Sheet | E41850 | cULus | |
5A (AC3/4) | -- | -- | -- | UL 489 MCP | -- | -- | -- | -- | -- | -- | Instruction Sheet | E41850 | cULus |
104K05ZQ02
104K0-5ZQ02
104-K05ZQ02
104K0 5ZQ02
104 K05ZQ02
Назад в раздел
|
QUAD Industry GMBH