| CONTACTOR COMBINATION, STAR-DELTA (PREASSEMBLED) SIDE-MOUNTING ON TIME RELAY, AC-3 22/30KW/400 V, 3-POLE, SIZE S2,S2,S0,EL. LOCK. DEVICE, SCREW CONNECTION, AC 110V, 50/60HZ |
|
General details: |
Product brand name | | SIRIUS |
product designation | | contactor assembly |
Product function | | wye-delta-contactor |
Size of the contactor | | S2, S2, S0 |
Protection class IP / on the front | | IP20 |
Degree of pollution | | 3 |
Insulation voltage / with degree of pollution 3 / rated value | V | 690 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Ambient temperature | | |
| °C | -25… +60 |
| °C | -55… +80 |
| °C | -55… +80 |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | K |
- according to DIN EN 61346-2
| | Q |
Mechanical operating cycles as operating time | | |
- of the main contacts / typical
| | 10,000,000 |
- of the auxiliary contacts / typical
| | 10,000,000 |
- of the contactor with added auxiliary switch block / typical
| | 10,000,000 |
|
Main circuit: |
Number of poles / for main current circuit | | 3 |
Number of NC contacts / for main contacts | | 0 |
Operating voltage / at AC-3 / rated value / maximum | V | 690 |
Operating current / at AC-3 / at 400 V / rated value | A | 65 |
Service power / at AC-3 | | |
| kW | 30 |
| kW | 35 |
| kW | 34 |
|
Steuerstromkreis/Ansteuerung: |
Design of activation | | conventional |
Design of the surge suppressor | | without |
Type of voltage / of the controlled supply voltage | | AC |
Control supply voltage frequency | | |
| Hz | 50 |
| Hz | 60 |
Control supply voltage / 1 | | |
- at 50 Hz / for AC / rated value
| V | 110 |
- at 60 Hz / for AC / rated value
| V | 110 |
Working range factor supply voltage rated value / of the magnet coil | | |
| | |
| | 0.8… 1.1 |
| | |
| | 0.85… 1.1 |
| | 0.8… 1.1 |
|
Auxiliary circuit: |
Product extension / auxiliary switch | | Yes |
Number of NC contacts / for auxiliary contacts | | |
| | 4 |
| | 0 |
Number of NO contacts / for auxiliary contacts | | |
| | 4 |
| | 0 |
|
Short-circuit: | | |
Design of the fuse link | | |
- for short-circuit protection of the auxiliary switch / required
| | fuse gL/gG: 10 A |
- for short-circuit protection of the main circuit
| | |
- with type of assignment 1 / required
| | fuse gL/gG: 125 A |
- at type of coordination 2 / required
| | fuse gL/gG: 63 A |
|
Einbau/Befestigung/Abmessung: | | |
Built in orientation | | with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back |
Type of mounting | | screw fixing |
Width | mm | 178 |
Height | mm | 140 |
Depth | mm | 169 |
Distance, to be maintained, to the ranks assembly / sidewards | mm | 0 |
Distance, to be maintained, to earthed part / sidewards | mm | 0 |
Distance, to be maintained, conductive elements | | |
| mm | 0 |
|
Anschlüsse/Klemmen |
Design of the electrical connection / for main current circuit | | screw-type terminals |
|
Approbationen/ Zertifikate | | |
Verification of suitability | | CE / UL / CCC / GL / LRS / BV / DNV / RMRS / RINA / PRS / ABS |
General Product Approval | Shipping Approval | ROSTEST | | |
| |
|
last change: | Aug 22, 2011 |