| MOLDED CASE CIRC.BREAKER 3RV1 FOR STARTER COMBINATION STANDARD SWITCHING CAPACITY RATED CURRENT IN=52A MAGNETIC RELEASE SHORT-CIRCUIT PROTECTION ADJUSTABLE 6-13XLN ICU =85KA AT 400V 3-POLE, SCREW TERMINAL INCL. PHASE BARRIERS |
|
General technical data: |
product brand name | | SIRIUS |
product designation | | molded-case circuit breaker |
Size of the circuit-breaker | | 3RV1.5 |
Degree of pollution | | 3 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Protection class IP / on the front | | IP20 |
Ambient temperature | | |
| °C | -40… +70 |
| °C | -25… +70 |
| °C | 70… -40 |
Resistance against shock | | 25g / 11 ms |
Insulation voltage / rated value | V | 800 |
Impulse voltage resistance / rated value | V | 8,000 |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | Q |
- according to DIN EN 61346-2
| | Q |
Mechanical operating cycles as operating time / of the main contacts / typical | | 25,000 |
Type of the driving mechanism / motor drive | | No |
Design of the operating mechanism | | toggle handle |
Product function | | |
| | No |
- phase disturbance recognition
| | No |
Product component | | |
| | No |
- undervoltage release mechanism
| | No |
| | No |
Product extension / optional / motor drive | | No |
|
Main circuit: |
Number of poles / for main current circuit | | 3 |
type of voltage | | AC |
Operating voltage / at AC-3 / rated value / maximum | V | 690 |
Operating current / at AC-3 / at 400 V / rated value | A | 52 |
Service power / at AC-3 | | |
| kW | 22 |
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum | 1/h | 15 |
Arrangement of electrical connectors / for main current circuit | | front side |
Adjustable response current | | |
- of the non-delayed short-circuit release
| A | 312… 624 |
Continuous current / rated value | A | 52 |
Product extension / auxiliary switch | | Yes |
|
Auxiliary circuit: |
Number of NC contacts / for auxiliary contacts / instantaneous switching | | 0 |
Number of NO contacts / for auxiliary contacts / instantaneous switching | | 0 |
Number of change-over switches / for auxiliary contacts | | 0 |
|
Inputs/ Outputs: | | |
Number of digital inputs | | 0 |
|
Short-circuit: |
Breaking capacity limit short-circuit current (lcu) | | |
| kA | 85 |
| kA | 50 |
| kA | 10 |
Design of the electrical connection / for auxiliary and control current circuit | | screw-type terminals |
Design of the overcurrent release and short-circuit release | | magnetic |
|
Installation/mounting/dimensions: |
Built in orientation | | any |
Type of mounting | | screw fixing |
Width | mm | 90 |
Height | mm | 130 |
Depth | mm | 70 |
Distance, to be maintained, to the ranks assembly | | |
| mm | 0 |
| mm | 0 |
Product function / removable terminal for auxiliary and control circuit | | No |
|
Connections: |
Design of the electrical connection | | |
| | screw-type terminals |
|
Certificates/approvals: | | |
General Product Approval | Test Certificates | Shipping Approval | other | ROSTEST | Manufacturer | Manufacturer | other | |
|
Safety: | | |
Protection against electrical shock | | finger-safe |
|
Further information: |
Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs |
Industry Mall (Online ordering system) http://www.siemens.com/industrial-controls/mall |
CAx-Online-Generator http://www.siemens.com/cax |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3RV1353-6PM10/all |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RV1353-6PM10 |
|
|
| |
|
last change: | Feb 27, 2012 |