| DIGITAL MONITORING RELAY CURRENT MONITORING, 22.5MM FOR IO-LINK 0.05 TO 10.0A AC/DC OVER- AND UNDERCURRENT CONVERTER SCALING FACTOR HYSTERESIS 0.01 TO 5.0A ON DELAY TIME TRIPPING DELAY TIME 1 CHANGE-OVER CONTACT, SCREW TERMINAL |
Product function | | Current monitoring relay |
|
Measuring circuit: | | |
Number of poles / for main current circuit | | 1 |
Type of current / for monitoring | | AC/DC |
Measurable current | A | 0.05… 10 |
| mA | 50… 750,000 |
Measurable line frequency | Hz | 500… 40 |
Adjustable response current | | |
| A | 0.05… 10 |
| A | 0.05… 10 |
Adjustable response delay time | | |
| s | 0… 999.9 |
- with lower or upper limit violation
| s | 0… 999.9 |
Adjustable switching hysteresis for measured current value | mA | 5… 10 |
Operating voltage | | |
| V | 24… 24 |
Response time / maximum | ms | 450 |
Relative metering precision | % | 5 |
Precision of digital display | | +/-1 digit |
Relative temperature-related measurement deviation | % | 5 |
Relative repeat accuracy | % | 1 |
|
General technical details: |
Design of the display | | LCD |
Product function | | |
- overcurrent recognition of 1 phase
| | Yes |
- overcurrent recognition of 3 phases
| | No |
- undercurrent recognition of 1 phase
| | Yes |
- undercurrent recognition of 3 phases
| | No |
- overcurrent recognition DC
| | Yes |
- undercurrent recognition DC
| | Yes |
- current window recognition DC
| | Yes |
| | Yes |
| | Yes |
- open-circuit or closed-circuit current principle
| | Yes |
Starting time / after the control supply voltage has been applied | ms | 1,000 |
Type of voltage / of supply voltage | | DC |
Supply voltage / 1 | | |
| V | 24 |
| V | 18… 30 |
Impulse voltage resistance / rated value | kV | 6 |
Recorded real power | W | 2 |
Protection class IP | | IP20 |
Electromagnetic compatibility | | IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4 |
Resistance against vibration / according to IEC 60068-2-6 | | 1
6 Hz: 15 mm, 6
500 Hz: 2g |
Resistance against shock / according to IEC 60068-2-27 | | sinusoidal half-wave 15g / 11 ms |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV |
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
Electrostatic discharge / according to IEC 61000-4-2 | | 6 kV contact discharge / 8 kV air discharge |
Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
Maximum permissible voltage for safe disconnection | | |
- between control and auxiliary circuit
| V | 690 |
- between auxiliary circuit and auxiliary circuit
| V | 300 |
Degree of pollution | | 2 |
Ambient temperature | | |
| °C | -25… +60 |
| °C | -40… +85 |
| °C | -40… +85 |
Galvanic isolation | | |
- between entrance and outlet
| | Yes |
- between the voltage supply and other circuits
| | Yes |
|
Communication: | | |
Type of voltage supply / via input/ output link master | | Yes |
IO-Link transfer rate | | COM2 (38,4 kBaud) |
Protocol / will be supported / IO-Link protocol | | Yes |
Data volume | | |
- of the address range of the outputs / with cyclical transfer
| byte | 2 |
- of the address range of the inputs / with cyclical transfer
| byte | 4 |
Point-to-point cycle time / between master and IO-Link device / minimum | ms | 10 |
|
Mechanical design: |
Width | mm | 22.5 |
Height | mm | 92 |
Depth | mm | 91 |
Built in orientation | | any |
Distance, to be maintained, to earthed part | | |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 0 |