SIMATIC SC,ELECTRONIC SUBMODULE 1 AO, 4..20MA, +/-20MA

Артикул: 6ES7124-1GA00-0AB0
Наименование: SIMATIC SC,ELECTRONIC SUBMODULE 1 AO, 4..20MA, +/-20MA (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC SC,ELECTRONIC SUBMODULE 1 AO, 4..20MA, +/-20MA
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1996-11-30 2005-10-01 2006-10-01 2015-10-01
SIMATIC SC,ELECTRONIC SUBMODULE 1 AO, 4..20MA, +/-20MA
Supply voltage
Rated value (DC) 24 V
Reverse polarity protection Yes
Input current
from supply voltage L+, max. 50 mA
Power losses
Power loss, max. 1 W
Hardware configuration
Rack
Required terminal block TB 16SC
Analog outputs
Number of analog outputs 1
Current output, no-load voltage, max. 16 V
Output ranges, current
0 to 20 mA Yes
4 to 20 mA Yes
Connection of actuators
for current output 2-conductor connection Yes
Load impedance (in rated range of output)
with current outputs, max. 600 Ω; at common-mode voltage 2 V, max. 500 ohms; at common-mode voltage 0 V, max. 600 ohms; idle test
with current outputs, inductive load, max. 1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA 15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Current, max. 50 mA; DC
Cable length
Cable length, shielded, max. 200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution (incl. overrange) S7 representation: 0 to 20 mA, 4 to 20 mA; S5 representation: 12 bits, 12 bits
Resolution with overrange (bit including sign), max. 12 bit
Conversion time (per channel) 5 ms
Settling time
for resistive load 0.1 ms
for inductive load 0.5 ms
Errors/accuracies
Linearity error (relative to output area) +/- 0,06 %
Temperature error (relative to output area) +/- 0,01 %/K
Repeat accuracy in settled status at 25 °C (relative to output area) +/- 0,1 %
Operational limit in overall temperature range
Current, relative to output area +/- 1,0 %
Basic error limit (operational limit at 25 °C)
Current, relative to output area +/- 0,7 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Common mode interference (UCM < Vss AC (50 Hz)), min. 30 dB
Interrupts/diagnostics/status information
Substitute values connectable No
Alarms
Alarms No
Diagnostic alarm No
Galvanic isolation
Galvanic isolation analog outputs
between the channels and the backplane bus No; Optocoupler
between the channels and the power supply of the electronics No
Permissible potential difference
between reference point of load and QV-(UCM) 2 V DC / 2 Vpp AC
Isolation
Isolation checked with 1500 V AC
Dimensions
Width 20 mm
Height 64 mm
Depth 51 mm
Required slots 2; from 8
Weight
Weight, approx. 25 g
Status Feb 27, 2012