SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE, FOR ET 200B, W=235MM, 16DI, 120/230V AC

Артикул: 6ES7131-0HF00-0XB0
Наименование: SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE, FOR ET 200B, W=235MM, 16DI, 120/230V AC (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE, FOR ET 200B, W=235MM, 16DI, 120/230V AC
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-10-01 2005-10-01 2006-10-01 2015-10-01
SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE, FOR ET 200B, W=235MM, 16DI, 120/230V AC
Input current
Rated value at 120 V AC 6.5 mA; at 60 Hz
Rated value at 230 V AC 10.5 mA; at 50 Hz
from supply voltage L1, max. 60 mA
Power losses
Power loss, typ. 6 W; at 230 V; 4.5 W at 120 V
Hardware configuration
Rack
Required terminal block TB6/AC
Digital inputs
Number/binary inputs 16
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Input voltage
Rated value, AC 120/230 V AC
for signal "0" 0 to 40 V
for signal "1" 79 to 264 V
Input current
for signal "1", typ. 3 mA; 3 to 16 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min. 0 ms
at "0" to "1", max. 25 ms
Cable length
Cable length unshielded, max. 600 m
Encoder
Connectable encoders
2-wire sensor No
Permissible quiescent current (2-wire sensor), max. 2 mA
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
Bus fault BF (red) Yes
Run mode RUN (green) Yes
Status indicator digital input (green) Yes
Galvanic isolation
between electronic block and PROFIBUS DP Yes; 500 V DC to the logic, 1500 V AC to connecting terminals
Galvanic isolation digital inputs
Galvanic isolation digital inputs Yes; Optocoupler
between the channels, in groups of 4
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 15 %
Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20 Yes
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width 235 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weight
Weight, approx. 811 g; EB and TB
Status Mar 12, 2012