SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD

Артикул: 6ES7132-0GF00-0XB0
Наименование: SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-10-01 2005-10-01 2006-10-01 2015-10-01
SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD
Supply voltage
24 V DC Yes; L3+; value at t < 0.5 s: 35 V
permissible range, lower limit (DC) 18.5 V
permissible range, upper limit (DC) 30.2 V
Input current
Current consumption, max. 130 mA; from L3+; logic
I²t 0.05 A²·s; with starting current inrush
Power losses
Power loss, typ. 2 W
Hardware configuration
Rack
Required terminal block TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC
Digital outputs
Number/binary outputs 8; Relay
Functionality/short-circuit strength No
Controlling a digital input Yes
Output voltage
Rated value (DC) 24 V; 24 to 60 V DC
Switching frequency
with resistive load, max. 10 Hz
with inductive load, max. 2 Hz
Relay outputs
Switching capacity of contacts
with inductive load, max. 0.5 A; at 30 V DC
Switching frequency/contacts/at ohmic load/maximum 2 A; at 24 V DC; max. 1.5 A at 48 V DC; max. 1 A at 60 V DC
Thermal continuous current, max. 5 A
Cable length
Cable length unshielded, max. 100 m
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s
SYNC capability Yes
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
Bus fault BF (red) Yes
Run mode RUN (green) Yes
Status indicator digital output (green) Yes
Galvanic isolation
between electronic block and PROFIBUS DP Yes
Galvanic isolation digital outputs
Galvanic isolation digital outputs Yes
between the channels, in groups of 1
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 15 %
Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20 Yes
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width 160 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weight
Weight, approx. 650 g; EB and TB
Status Mar 5, 2012