SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, DIGITAL, 16 DO 0,5A, 24V DC, EXPANDABLE WITH MAX. 16 CHANNELS W. TERM. BLOCK TB 16SC OF SMART CONNECT

Артикул: 6ES7132-1BH11-0XB0
Наименование: SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, DIGITAL, 16 DO 0,5A, 24V DC, EXPANDABLE WITH MAX. 16 CHANNELS W. TERM. BLOCK TB 16SC OF SMART CONNECT (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, DIGITAL, 16 DO 0,5A, 24V DC, EXPANDABLE WITH MAX. 16 CHANNELS W. TERM. BLOCK TB 16SC OF SMART CONNECT
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1996-11-30 2005-10-01 2006-10-01 2015-10-01
SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, DIGITAL, 16 DO 0,5A, 24V DC, EXPANDABLE WITH MAX. 16 CHANNELS W. TERM. BLOCK TB 16SC OF SMART CONNECT
General information
Vendor identification (VendorID) 8028h
Supply voltage
Mains buffering
Mains buffering, min. 20 ms
Load voltage L+
Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 50 mA
from supply voltage L+, max. 180 mA
Power losses
Power loss, typ. 4 W
Hardware configuration
Rack
Required terminal block TB 16L (expansion: digital and analog with SIMATIC SC)
Digital outputs
Number/binary outputs 16
Functionality/short-circuit strength Yes; Electronic
Response threshold, typ. 0.7 A
Limitation of inductive shutdown voltage to Typ. (L1+ or L2+ / L3+) -55 V
Lamp load, max. 5 W
Controlling a digital input Yes
Load resistance range
lower limit 41 Ω
upper limit 28000 Ω
Output voltage
Rated value (DC) 24 V
for signal "1", min. Ua - 3 V
Output current
for signal "1" rated value 500 mA
for signal "1" permissible range for 0 to 40 °C, min. 1 mA
for signal "1" permissible range for 0 to 40 °C, max. 500 mA
for signal "1" permissible range for 0 to 60 °C, max. 0.5 A
for signal "0" residual current, max. 1 mA
Output delay with resistive load
0 to "1", max. 50 ms
1 to "0", max. 200 ms
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes; only outputs of the same group
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 8 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 60 °C, max. 4 A
Total current of the outputs (per module)
horizontal installation
up to 40 °C, max. 3 A
up to 60 °C, max. 2 A
all other mounting positions
up to 40 °C, max. 2 A
Relay outputs
Rated input voltage of relay coil L+ (DC) 24 V
Reverse polarity protection Yes
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Interfaces
PROFIBUS DP
Transmission rate, max. 1.5 Mbit/s
SYNC capability Yes
FREECE capability Yes; for SC inputs
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Alarms
Alarms No
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
Bus fault BF (red) Yes
Group error SF (red) Yes
Status indicator digital output (green) Yes
Monitoring 24 V voltage supply ON (green) Yes
Galvanic isolation
Galvanic isolation digital outputs
between the channels No
between the channels and PROFIBUS DP Yes
Isolation
Isolation checked with 500 V DC
Dimensions
Width 145 mm
Height 60 mm
Depth 60.5 mm
Weight
Weight, approx. 130 g
Status Mar 5, 2012

Назад в раздел