| SIMATIC DP, ELECT. SUBMODULE FOR ET 200ISP, 4 DO, DC 25.5V/22MA, "L"-SHUT DOWN |
|
Input current |
from load voltage L+ (without load), max. | 400 mA |
Power losses |
Power loss, typ. | 2.8 W |
Address area |
Address space per module |
without packing | 2 byte |
Digital inputs |
Cable length |
Cable length, shielded, max. | 20 m |
Cable length unshielded, max. | 20 m |
Digital outputs |
Number/binary outputs | 4; additionally 1 intrinsically-safe input for L shutdown |
Functionality/short-circuit strength | Yes |
No-load voltage Uao (DC) | 25.5 V |
Internal resistor Ri | 260 Ω |
Trend key points E |
Voltage Ue (DC) | 19.8 V |
Current Ie | 22 mA |
Output delay with resistive load |
0 to "1", max. | 2 ms |
1 to "0", max. | 1.5 ms |
Parallel switching of 2 outputs |
for increased power | No |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 2 Hz |
Cable length |
Cable length, shielded, max. | 500 m |
Cable length unshielded, max. | 500 m |
Interrupts/diagnostics/status information |
Status indicator | Yes |
Substitute values connectable | Yes |
Alarms |
Diagnostic alarm | Yes; Parameterizable |
Diagnostic messages |
Diagnostic information readable | Yes |
Wire break | Yes; R > 10 kohms, I < 100 µA |
Short circuit | Yes; R < 80 ohms |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes; Per channel |
Parameter |
Diagnosis: wire break | Yes |
Diagnosis: short circuit | Yes |
Behavior on CPU/Master STOP, channel-wise | Substitute a value/keep last value |
Ex(i) characteristics |
Max. values of output circuits (per channel) |
Co (permissible external capacity), max. | 81 nF; For IIC, 651 nF for IIB |
Io (short-circuit current), max. | 110 mA |
Lo (permissible external inductivity), max. | 1.7 mH; For IIC, 11.5 mH for IIB |
Po (power of load), max. | 764 mW |
Uo (output no-load voltage), max. | 27.9 V |
Galvanic isolation |
Galvanic isolation digital outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | Yes |
Permissible potential difference |
between different circuits | 60V DC/30V AC |
Standards, approvals, certificates |
CE mark | Yes |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) | II 2 G (1) GD and I M2 Ex ib[ia][iaD] IIC T4; Ex ib [ia] I |
Type of protection acc. to KEMA | 04 ATEX 1249 |
Dimensions |
Width | 30 mm |
Height | 129 mm |
Depth | 136.5 mm |
Weight |
Weight, approx. | 255 g |
Status | Mar 12, 2012 |