SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8DE 24V DC; 8DA 24V DC, 0,5A WITH INTEGRATED HW SWITCH-OFF OF THE OUTPUTS

Артикул: 6ES7133-0BH10-0XB0
Наименование: SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8DE 24V DC; 8DA 24V DC, 0,5A WITH INTEGRATED HW SWITCH-OFF OF THE OUTPUTS (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8DE 24V DC; 8DA 24V DC, 0,5A WITH INTEGRATED HW SWITCH-OFF OF THE OUTPUTS
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-10-01 2005-10-01 2006-10-01 2015-10-01
SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8DE 24V DC; 8DA 24V DC, 0,5A WITH INTEGRATED HW SWITCH-OFF OF THE OUTPUTS
Supply voltage
24 V DC Yes; L1+, L3+; value at t < 0.5 s: 35 V
permissible range, lower limit (DC) 18.5 V
permissible range, upper limit (DC) 30.2 V
Input current
Current consumption, typ. 70 mA; from L3+; logic
Current consumption, max. 500 mA; from L3+; sensor
I²t 0.05 A²·s; with starting current inrush
Power losses
Power loss, max. 3.8 W
Hardware configuration
Rack
Required terminal block TB1/DC, TB1-4/DC, TB3/DC
Digital inputs
Number/binary inputs 8
Input voltage
Rated value, DC 24 V
for signal "0" -30 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 4 mA; At 24 V min. 2 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min. 3 ms
Cable length
Cable length unshielded, max. 100 m
Digital outputs
Number/binary outputs 8
Functionality/short-circuit strength Yes; Electronic
Limitation of inductive shutdown voltage to typically (L1+) -55 V
Lamp load, max. 5 W
Controlling a digital input Yes
Output voltage
Rated value (DC) 24 V
for signal "0", max. 2 V; Idling
for signal "1", min. UE -3 V
Output current
for signal "1" permissible range for 0 to 60 °C, min. 0.5 A; in one group
for signal "0" residual current, max. 1 mA
Output delay with resistive load
0 to "1", max. 50 ms
1 to "0", max. 100 ms
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 8 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 60 °C, max. 2 A
Cable length
Cable length unshielded, max. 100 m
Encoder
Connectable encoders
2-wire BEROS Yes
permissible quiescent current (2-wire BEROS), max. 1.5 mA
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s
SYNC capability Yes
FREECE capability Yes
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
Bus fault BF (red) Yes
Run mode RUN (green) Yes
Status indicator digital input (green) Yes
Galvanic isolation
between electronic block and PROFIBUS DP Yes
Galvanic isolation digital inputs
Galvanic isolation digital inputs No
Galvanic isolation digital outputs
Galvanic isolation digital outputs No
between the channels, in groups of 8
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 15 %
Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20 Yes
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width 160 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weight
Weight, approx. 650 g; EB and TB
Status Mar 5, 2012

Назад в раздел