| SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD |
|
Hardware configuration |
Rack |
Required terminal block | TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC |
Digital inputs |
Number/binary inputs | 24 |
Input voltage |
Rated value, DC | 24 V |
for signal "0" | -30 to +5 V |
for signal "1" | 13 to 30 V |
Input current |
for signal "1", typ. | 4 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", max. | 0.2 ms |
Cable length |
Cable length unshielded, max. | 100 m |
Digital outputs |
Number/binary outputs | 8 |
Functionality/short-circuit strength | Yes; Electronic |
Output voltage |
Rated value (DC) | 24 V |
for signal "0", max. | 2 V; Idling |
for signal "1", min. | UE -3 V |
Output current |
for signal "1" permissible range for 0 to 60 °C, min. | 0.5 A; in one group |
for signal "0" residual current, max. | 1 mA |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 8 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
up to 60 °C, max. | 2 A |
Cable length |
Cable length unshielded, max. | 100 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
Galvanic isolation |
between electronic block and PROFIBUS DP | Yes |
Galvanic isolation digital inputs |
Galvanic isolation digital inputs | No |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Status | Mar 5, 2012 |