SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI HART, 4DMU, FOR CONNECTION OF HART 4-WIRE TRANSDUCER

Артикул: 6ES7134-7TD50-0AB0
Наименование: SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI HART, 4DMU, FOR CONNECTION OF HART 4-WIRE TRANSDUCER (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI HART, 4DMU, FOR CONNECTION OF HART 4-WIRE TRANSDUCER
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2004-10-15
Manuals weitere>>
Устройство децентрализованной периферии ET 200 iSP  2007-03-14
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI HART, 4DMU, FOR CONNECTION OF HART 4-WIRE TRANSDUCER
Input current
from supply voltage L+, max. 30 mA
Power losses
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 4
Cycle time (all channels) max. 120 ms; 30 ms basic conversion time x 4 channels with 60 Hz, 50 Hz interference frequency suppression
permissible input current for current input (destruction limit), max. 50 mA
Technical unit for temperature measurement adjustable Yes
Input ranges
Voltage No
Current Yes
Thermocouple No
Resistance thermometer No
Resistance No
Input ranges (rated values), currents
4 to 20 mA Yes; Min. 295 Ohm
Cable length
Cable length, shielded, max. 500 m
Analog value creation
Measurement principle integrating (Sigma-Delta)
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 12 bit; + sign
Integration time, parameterizable Yes
Basic conversion time, including integration time, ms 30
Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Smoothing of measured values
Parameterizable Yes; in 4 stages
Step: None Yes; 1 x cycle time
Step: low Yes; 4 x cycle time
Step: Medium Yes; 32 x cycle time
Step: High Yes; 64 x cycle time
Encoder
Connection of signal encoders
for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input area) +/- 0.015 %
Temperature error (relative to input area) +/- 0.005 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in settled status at 25 °C (relative to input area) +/- 0.01 %
Operational limit in overall temperature range
Current, relative to input area +/- 0.15 %
Basic error limit (operational limit at 25 °C)
Current, relative to input area +/- 0.1 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes; Parameterizable
Limit value alarm Yes; Parameterizable
Diagnostic messages
Diagnostic information readable Yes
Wire break Yes
Diagnostics indication LED
Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
between the channels No
between the channels and the backplane bus Yes
Standards, approvals, certificates
CE mark Yes
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
Type of protection acc. to KEMA 04 ATEX 1245
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weight
Weight, approx. 230 g
Status Mar 12, 2012

Назад в раздел