SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S

Артикул: 6ES7135-0HF01-0XB0
Наименование: SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1996-07-01 2005-10-01 2006-10-01 2015-10-01
SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S
Supply voltage
Rated value (DC) 24 V; Value at t < 0.5 s: 35 V
permissible range, lower limit (DC) 18.5 V
permissible range, upper limit (DC) 30.2 V
Input current
from supply voltage L+, max. 200 mA; Logic
Power losses
Power loss, typ. 2.4 W
Hardware configuration
Rack
Required terminal block TB8
Digital outputs
Load resistance range
Load impedance in rated range of output , capacitive load, max. 1 µF
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes; Electronic; max. 1 output in parallel
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes
-10 to +10 V Yes
Output ranges, current
0 to 20 mA Yes
4 to 20 mA Yes
Connection of actuators
for voltage output 2-conductor connection Yes
for voltage output 4-conductor connection Yes
for current output 2-conductor connection Yes
Load impedance (in rated range of output)
with current outputs, max. 300 Ω
with current outputs, inductive load, max. 1 mH
Cable length
Cable length, shielded, max. 100 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 11 bit; Two's complement
Conversion time (per channel) 1 ms
Settling time
for resistive load 0.1 ms
for capacitive load 3.3 ms
for inductive load 0.5 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz) +/- 0.05 %
Linearity error (relative to output area) +/- 0.05 %
Temperature error (relative to output area) +/- 0.02 %
Crosstalk between the outputs, min. 40 dB
Repeat accuracy in settled status at 25 °C (relative to output area) +/- 0.05 %
Operational limit in overall temperature range
Voltage, relative to output area +/- 0.05 %
Current, relative to output area +/- 1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output area +/- 0.2 %
Current, relative to output area +/- 0.3 %
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes; Parameterizable
Diagnostics indication LED
Bus fault BF (red) Yes
Run mode RUN (green) Yes
Galvanic isolation
between electronic block and PROFIBUS DP Yes
Galvanic isolation analog outputs
Galvanic isolation analog outputs No
Ambient conditions
Operating temperature
horizontal installation, min. 0 °C
horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 15 %
Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20 Yes
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width 160 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weight
Weight, approx. 550 g; EB and TB
Status Feb 27, 2012

Назад в раздел