SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 1 POS-INC ANALOG, CONTROLLED POSITIONING WITH ANALOG OUTPUT FOR 5V INCREMENTAL ENCODER, 30MM WIDE

Артикул: 6ES7138-4DJ00-0AB0
Наименование: SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 1 POS-INC ANALOG, CONTROLLED POSITIONING WITH ANALOG OUTPUT FOR 5V INCREMENTAL ENCODER, 30MM WIDE (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 1 POS-INC ANALOG, CONTROLLED POSITIONING WITH ANALOG OUTPUT FOR 5V INCREMENTAL ENCODER, 30MM WIDE
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-11-01 2005-02-01 2006-10-01 2015-02-01
Manuals weitere>>
ET 200S Distributed I/O System  2004-09-14
SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 1 POS-INC ANALOG, CONTROLLED POSITIONING WITH ANALOG OUTPUT FOR 5V INCREMENTAL ENCODER, 30MM WIDE
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 50 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 2 W
Hardware configuration
Module exchange
Hot swapping the IM-DP Yes
Module exchange under process voltage Yes
Digital inputs
Number/binary inputs 3
Input characteristic curve acc. to IEC 61131, Type 2 Yes
Input voltage
Rated value, DC 24 V
for signal "0" -30 to +5 V
for signal "1" 11 to 30 V
Input current
for signal "0", max. (permissible quiescent current) 2 mA
for signal "1", typ. 9 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min. 500 µs
Cable length
Cable length unshielded, max. 50 m
Digital outputs
Number/binary outputs 1
Functionality/short-circuit strength Yes
Response threshold, typ. 0.7 to 1.8 A
Lamp load, max. 5 W
Controlling a digital input Yes
Output voltage
Rated value (DC) 24 V
for signal "0", max. 3 V
for signal "1", min. L+ (-1 V)
Output current
for signal "1" permissible range for 0 to 60 °C, min. 7 mA
for signal "1" permissible range for 0 to 60 °C, max. 600 mA
for signal "0" residual current, max. 0.3 mA
Output delay with resistive load
0 to "1", max. 1.3 ms; typically 150 µs
1 to "0", max. 200 µs; typically 150 µs
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 2 Hz
on lamp load, max. 10 Hz
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Analog outputs
Number of analog outputs 1
Function Output of speed setpoint
Output ranges, voltage
0 to 10 V Yes
-10 to +10 V Yes
Load impedance (in rated range of output)
with voltage outputs, min. 1 kΩ
with voltage outputs, capacitive load, max. 1 µF
Analog value creation
Update time of the feedback messages 2 ms
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 14 bit; +/-10 V: 14 bits, 0 to 10 V: 13 bits
Settling time
for resistive load 0.1 ms
for capacitive load 0.5 ms
for inductive load 0.5 ms
Encoder
Number of connectable encoders, max. 1
Connectable encoders
Incremental encoder (symmetrical) Yes
2-wire sensor Yes; Type 2
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz) +/- 0,02 %
Linearity error (relative to output area) +/- 0,02 %
Temperature error (relative to output area) +/- 0,01 %/K
Repeat accuracy in settled status at 25 °C (relative to output area) +/- 0,05 %
Operational limit in overall temperature range
Voltage, relative to output area +/- 0,4 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output area +/- 0,2 %
Response times
Latch 400 µs; typ.
Response time at switchover/switchoff time 0.1 µs; 0.1 to 0.2 µs
Interrupts/diagnostics/status information
Diagnostics indication LED
Actual value falling DN (green) Yes
Actual value rising UP (green) Yes
Positioning mode POS (green) Yes
Group error SF (red) Yes
Status indicator digital input (green) Yes
Counter
Counter input 5 V
Number 1
Type RS 422
Terminating resistor 330 Ω
Differential input voltage min. 1 V
Counting frequency, max. 500 kHz
Positioning
Number of positioning outputs (axes) 1
Galvanic isolation
between the channels and backplane bus Yes
Dimensions
Width 30 mm
Height 81 mm
Depth 52 mm
Weight
Weight, approx. 65 g
Status Mar 12, 2012