SIMATIC DP, BASIC MOD. BM142 ET 200ECO: 16 DO DC 24 V/0.5 A, 8 X M12, DOUBLE-ASSIGNEMENT, IP65/67, CONN. BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY

Артикул: 6ES7142-3BH00-0XA0
Наименование: SIMATIC DP, BASIC MOD. BM142 ET 200ECO: 16 DO DC 24 V/0.5 A, 8 X M12, DOUBLE-ASSIGNEMENT, IP65/67, CONN. BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, BASIC MOD. BM142 ET 200ECO: 16 DO DC 24 V/0.5 A, 8 X M12, DOUBLE-ASSIGNEMENT, IP65/67, CONN. BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2003-02-28
SIMATIC DP, BASIC MOD. BM142 ET 200ECO: 16 DO DC 24 V/0.5 A, 8 X M12, DOUBLE-ASSIGNEMENT, IP65/67, CONN. BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY
General information
Vendor identification (VendorID) 80FBh
Supply voltage
Rated value (DC) 24 V
Reverse polarity protection Yes
Load voltage 2L+
Rated value (DC) 24 V
Reverse polarity protection Yes
Input current
from load voltage 2L+ (without load), max. 80 mA; typ.
from supply voltage 1L+, max. 70 mA; typ.
Power losses
Power loss, typ. 4 W
Digital outputs
Number/binary outputs 16
Functionality/short-circuit strength Yes; Electronic
Response threshold, typ. 1.4 A (per channel)
Limitation of inductive shutdown voltage to 2L+ (-47 V)
Lamp load, max. 5 W
Controlling a digital input Yes
Load resistance range
lower limit 12 Ω
upper limit 4 kΩ
Output voltage
for signal "1", min. 2L+ (-0.8 V)
Output current
for signal "1" rated value 0.5 A
for signal "1" permissible range for 0 to 55 °C, min. 5 mA
for signal "1" permissible range for 0 to 55 °C, max. 1 A
for signal "0" residual current, max. 0.1 mA
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz; to IEC 947-5-1, DC13
on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 55 °C, max. 4 A; Please note the current carrying capacity of the cable!
Cable length
Cable length unshielded, max. 30 m
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 3 / 6 / 12 Mbit/s
Protocols
Further protocols
PROFIBUS DP protocol Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms
Alarms No
Diagnostic messages
Diagnostics Yes; Diagnostic information readable
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital output (green) Yes
Channel error indicator F (red) No
Galvanic isolation
between PROFIBUS DP and all other circuit components Yes
Galvanic isolation digital outputs
between the channels No
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 60 mm
Height 210 mm
Depth 28 mm
Weight
Weight, approx. 210 g
Status Mar 12, 2012