SIMATIC DP, BASIC MODULE BM143 ET 200ECO: 8DI/8DO, 2A; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY

Артикул: 6ES7143-3BH00-0XA0
Наименование: SIMATIC DP, BASIC MODULE BM143 ET 200ECO: 8DI/8DO, 2A; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, BASIC MODULE BM143 ET 200ECO: 8DI/8DO, 2A; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2002-06-01
SIMATIC DP, BASIC MODULE BM143 ET 200ECO: 8DI/8DO, 2A; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY
General information
Vendor identification (VendorID) 80DCh
Supply voltage
Rated value (DC) 24 V
Reverse polarity protection No
Load voltage 2L+
Rated value (DC) 24 V
Reverse polarity protection No
Input current
from load voltage 2L+ (without load), max. 60 mA; typ.
from supply voltage 1L+, max. 70 mA; typ.
Encoder supply
Number of outputs 8
Output voltage 24 V DC
Output current, rated value 0.75 A; up to 55°C max. 0.75 A (summation current)
Output current
Short-circuit protection Yes; Electronic
Power losses
Power loss, typ. 5 W
Digital inputs
Number/binary inputs 8
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs 8; All mounting positions up to 55 °C
Input voltage
Type of input voltage DC
Rated value, DC 24 V
for signal "0" -3 to +5 V
for signal "1" 13 to 30 V
Input current
for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", max. 3 ms; typ.
at "1" to "0", max. 3 ms; typ.
Digital outputs
Number/binary outputs 8
Functionality/short-circuit strength Yes; Electronic
Response threshold, typ. 4 A per channel
Limitation of inductive shutdown voltage to 2L+ (-44 V)
Lamp load, max. 10 W
Controlling a digital input Yes
Load resistance range
lower limit 12 Ω
upper limit 4 kΩ
Output voltage
for signal "1", min. 2L+ (-0.8 V)
Output current
for signal "1" rated value 2 A
for signal "1" permissible range for 0 to 55 °C, min. 5 mA
for signal "1" permissible range for 0 to 55 °C, max. 2.4 A
for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz; to IEC 947-5-1, DC13
on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 55 °C, max. 4 A; 4 A each for sockets X1, X3, X5, X7 and 4 A each for sockets X2, X4, X6, X8; note the current carrying capacity of the cable
Cable length
Cable length unshielded, max. 30 m
Encoder
Connectable encoders
2-wire sensor Yes
Permissible quiescent current (2-wire sensor), max. 1.5 mA
Interfaces
PROFIBUS DP
Transmission rate, max. 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 3 / 6 / 12 Mbit/s
Protocols
Further protocols
PROFIBUS DP protocol Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms
Alarms No
Diagnostic messages
Diagnostics Yes; Diagnostic information readable
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital output (green) Yes
Status indicator digital input (green) Yes
Channel error indicator F (red) No
Galvanic isolation
between PROFIBUS DP and all other circuit components Yes
Galvanic isolation digital inputs
between the channels No
Galvanic isolation digital outputs
between the channels No
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 60 mm
Height 210 mm
Depth 28 mm
Weight
Weight, approx. 210 g
Status Mar 12, 2012

Назад в раздел