SIMATIC DP, ELEKTRONIC MODULE FOR ET200PRO, 4 AI TC HIGH FEATURE, TC TYP B, E, J, K, L, N, R, S,T VOLTAGE +/- 80MV CHANNEL DIANOSTICS; INCL. BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY

Артикул: 6ES7144-4PF00-0AB0
Наименование: SIMATIC DP, ELEKTRONIC MODULE FOR ET200PRO, 4 AI TC HIGH FEATURE, TC TYP B, E, J, K, L, N, R, S,T VOLTAGE +/- 80MV CHANNEL DIANOSTICS; INCL. BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELEKTRONIC MODULE FOR ET200PRO, 4 AI TC HIGH FEATURE, TC TYP B, E, J, K, L, N, R, S,T VOLTAGE +/- 80MV CHANNEL DIANOSTICS; INCL. BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-07-30
Manuals weitere>>
Distributed I/O device ET 200pro  2005-12-16
SIMATIC DP, ELEKTRONIC MODULE FOR ET200PRO, 4 AI TC HIGH FEATURE, TC TYP B, E, J, K, L, N, R, S,T VOLTAGE +/- 80MV CHANNEL DIANOSTICS; INCL. BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY
Supply voltage
Load voltage L+
Rated value (DC) 24 V
Reverse polarity protection Yes; against destruction
Input current
from load voltage L+ (without load), max. 34 mA; typ.
from backplane bus 3.3 V DC, max. 20 mA; typ.
Power losses
Power loss, typ. 0.7 W
Address area
Address space per module
Address space per module, max. 8 byte
Analog inputs
Number of analog inputs 4
permissible input voltage for voltage input (destruction limit), max. 20 V
Cycle time (all channels) max. Number of active channels per module x basic conversion time
Input ranges
Voltage Yes
Thermocouple Yes
Input ranges (rated values), voltages
-80 mV to +80 mV Yes
Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), thermoelements
Type B Yes
Input resistance (Type B) 10 MΩ
Type E Yes
Input resistance (Type E) 10 MΩ
Type J Yes
Input resistance (type J) 10 MΩ
Type K Yes
Input resistance (Type K) 10 MΩ
Type L Yes
Input resistance (Type L) 10 MΩ
Type N Yes
Input resistance (Type N) 10 MΩ
Type R Yes
Input resistance (Type R) 10 MΩ
Type S Yes
Input resistance (Type S) 10 MΩ
Type T Yes
Input resistance (Type T) 10 MΩ
Thermocouple (TC)
[nicht versorgt: TAK_ABT261_001_000]
internal temperature compensation Yes
external temperature compensation with compensations socket Yes
Cable length
Cable length, shielded, max. 30 m
Analog value creation
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 15 bit; + sign
Integration time, ms 2.5/16.67/20/100 ms
Interference voltage suppression for interference frequency f1 in Hz 10/50/60/400 Hz
Conversion time (per channel) 4.7/19/22/102 ms
Smoothing of measured values
Parameterizable Yes
Step: None Yes; 1 x cycle time
Step: low Yes; 4 x cycle time
Step: Medium Yes; 16 x cycle time
Step: High Yes; 64 x cycle time
Errors/accuracies
Temperature error (relative to input area) Positive temperature
Crosstalk between the inputs, min. -90 dB; max.
Operational limit in overall temperature range
Voltage, relative to input area Positive temperature
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min. 42 dB
common mode voltage (USS < 2.5 V) , min. 85 dB; Interference voltage < 10 V
Interrupts/diagnostics/status information
Diagnostic messages
Wire break No
Overflow/underflow Yes
Diagnostics indication LED
Group error SF (red) Yes
Parameter
Measurement type/range Deactivated/ +/- 80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type N (NiCrSi-NiSi)/ TC-EL Typ E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC-EL Type L (Fe-CuNi)
Interference frequency suppression 10/50/60/400 Hz
Group diagnostics Yes
Overflow/underflow Yes
Comparison point None/internal/RTD(0)/dyn. ref. temp./fix. ref. temp.
Unit °C/°F/K
Galvanic isolation
Galvanic isolation analog inputs
between the channels No
between the channels and the backplane bus Yes
between the channels and the load voltage L+ Yes
Permissible potential difference
between the inputs (UCM) 20 Vpp AC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 45 mm
Height 130 mm
Depth 35 mm
Weight
Weight, approx. 150 g
Status Mar 12, 2012