SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67

Артикул: 6ES7144-6KD00-0AB0
Наименование: SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67 (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-04-30
SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67
General information
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0306H
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, typ. 110 mA
Encoder supply
Number of outputs 4
24 V encoder supply
Short-circuit protection Yes; Electronic at 1.4 A
Output current, max. 1 A
Power losses
Power loss, typ. 2.8 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for voltage/current measurement 4
Number of analog inputs for resistance/resistance thermometer measurement 4
permissible input voltage for voltage input (destruction limit), max. 28.8 V permanent, 35 V for max. 500 ms
Input ranges (rated values), voltages
0 to +10 V Yes
1 to 5 V Yes
-10 V to +10 V Yes
-80 mV to +80 mV Yes
Input ranges (rated values), currents
0 to 20 mA Yes
-20 to +20 mA Yes
4 to 20 mA Yes
Input ranges (rated values), thermoelements
Type E Yes
Type J Yes
Type K Yes
Type N Yes
Input ranges (rated values), resistance thermometers
Ni 100 Yes
Ni 1000 Yes
Ni 120 Yes
Ni 200 Yes
Ni 500 Yes
Pt 100 Yes
Pt 1000 Yes
Pt 200 Yes
Pt 500 Yes
Input ranges (rated values), resistors
0 to 150 ohms Yes
0 to 300 ohms Yes
0 to 600 ohms Yes
0 to 3000 ohms Yes
Thermocouple (TC)
Temperature compensation
Parameterizable Yes
internal temperature compensation Yes
external temperature compensation with compensations socket Yes
Cable length
Cable length, shielded, max. 30 m
Analog value creation
Analog value display SIMATIC S7 format
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution (incl. overrange) 15 bits + sign
Integration time, parameterizable Yes
Integration time, ms 2/16.67/20/100 ms
Interference voltage suppression for interference frequency f1 in Hz 500 / 60 / 50 / 10 Hz
Conversion time (per channel) 4/19/22/102 ms
Smoothing of measured values
Parameterizable Yes
Step: None Yes; 1 x cycle time
Step: low Yes; 4 x cycle time
Step: Medium Yes; 16 x cycle time
Step: High Yes; 64 x cycle time
Encoder
Number of connectable encoders, max. 8
Connection of signal encoders
for voltage measurement Yes
for current measurement as 2-wire transducer Yes
for current measurement as 4-wire transducer Yes
for resistance measurement with 2-conductor connection Yes
for resistance measurement with 3-conductor connection Yes
for resistance measurement with 4-conductor connection Yes
Errors/accuracies
Linearity error (relative to input area) +/- 0,01 %
Temperature error (relative to input area) U: 0.0035%/°C; I:0.006%/°C; RTD: 0.0005%/°C; TC: 0.0035%/°C
Crosstalk between the inputs, min. 85 dB
Repeat accuracy in settled status at 25 °C (relative to input area) +/- 0,008 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min. 46 dB
Common mode interference, min. 70 dB
Interfaces
Transmission procedure 100BASE-TX
Transmission rate, max. 100 Mbit/s
Supports protocol for PROFINET IO
Number of PROFINET interfaces 2
Autocrossing Yes
Automatic detection of transmission speed Yes
Integrated switch Yes
PROFINET IO Device
IRT with the option "high flexibility" supported Yes
Prioritized startup supported Yes
Protocols
Supports protocol for PROFINET IO Yes
Protocols (Ethernet)
SNMP Yes
DCP Yes
LLDP Yes
ping Yes
arp Yes
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostic information readable Yes
Monitoring the supply voltage Yes; Green "ON" LED
Short circuit encoder supply Yes; per module
Group error Yes; Red/yellow "SF/MT" LED
Overflow/underflow Yes
Galvanic isolation
between the load voltages Yes
between load voltage and all other switching components No
between Ethernet and electronics Yes
Назад в раздел