| SIMATIC DP, ET 200ECO PN, 4 AO U/I; 4 X M12, DEGREE OF PROTECTION IP67 |
|
General information |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0306H |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption, typ. | 280 mA |
Encoder supply |
Number of outputs | 4 |
24 V encoder supply |
Short-circuit protection | Yes; Electronic at 1.4 A |
Output current, max. | 1 A |
Power losses |
Power loss, typ. | 5.5 W |
Analog outputs |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 30 mA |
Current output, no-load voltage, max. | 20 V |
Output ranges, voltage |
0 to 10 V | Yes |
1 to 5 V | Yes |
-10 to +10 V | Yes |
Output ranges, current |
0 to 20 mA | Yes |
-20 to +20 mA | Yes |
4 to 20 mA | Yes |
Connection of actuators |
for voltage output 2-conductor connection | Yes |
for current output 2-conductor connection | Yes |
Load impedance (in rated range of output) |
with voltage outputs, min. | 1 kΩ |
with voltage outputs, capacitive load, max. | 1 µF |
with current outputs, max. | 600 Ω |
with current outputs, inductive load, max. | 1 mH |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA | 28.8 V permanent, 35 V for max. 500 ms |
Cable length |
Cable length, shielded, max. | 30 m |
Analog value creation |
Analog value display | SIMATIC S7 format |
Measurement principle | Resistor network |
Integrations and conversion time/ resolution per channel |
Resolution (incl. overrange) | 15 bits + sign |
Conversion time (per channel) | 1 ms |
Settling time |
for resistive load | 2 ms |
for capacitive load | 1.8 ms |
for inductive load | 2 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz) | U: ±0.6 mVrms; I: ±0.4 nArms |
Linearity error (relative to output area) | +/- 0,02 % |
Temperature error (relative to output area) | U: 0.001%/°C; I: 0.0025%/°C |
Crosstalk between the outputs, min. | 70 dB |
Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0,008 % |
Interfaces |
Transmission procedure | 100BASE-TX |
Transmission rate, max. | 100 Mbit/s |
Supports protocol for PROFINET IO |
Number of PROFINET interfaces | 2 |
Autocrossing | Yes |
Automatic detection of transmission speed | Yes |
Integrated switch | Yes |
PROFINET IO Device |
IRT with the option "high flexibility" supported | Yes |
Prioritized startup supported | Yes |
Protocols |
Supports protocol for PROFINET IO | Yes |
Protocols (Ethernet) |
SNMP | Yes |
DCP | Yes |
LLDP | Yes |
ping | Yes |
arp | Yes |
Interrupts/diagnostics/status information |
Status indicator | Yes |
Substitute values connectable | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Monitoring the supply voltage | Yes; Green "ON" LED |
Wire break | Yes; Channel-by-channel with current output |
Short circuit | Yes; Channel-by-channel with voltage output |
Group error | Yes; Red/yellow "SF/MT" LED |
Galvanic isolation |
between the load voltages | Yes |
between load voltage and all other switching components | No |
between Ethernet and electronics | Yes |
Galvanic isolation analog outputs |
between the channels | No |
Permissible potential difference |
between M internally and the outputs | 10 Vpp AC |
Degree and class of protection |
IP65 | Yes |
IP66 | Yes |
IP67 | Yes |
Connection method |
M12 | Yes |
Dimensions |
Width | 60 mm |
Height | 175 mm |
Depth | 49 mm |
Weight |
Weight | 930 g |
Status | Mar 12, 2012 |