| SIMATIC DP, PNEUMATIC INTERFACE FOR ET 200PRO 16 DO PNEUMATIC FOR COUPLING WITH FESTO VALVE BLOCK CPV-14 INCLUSIVE BUS MODULE |
|
Supply voltage |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Short-circuit protection | Yes |
Reverse polarity protection | Yes |
Input current |
from load voltage 2L+ (without load), max. | 20 mA |
from backplane bus 3.3 V DC, max. | 25 mA |
Power losses |
Power loss, typ. | 3.7 W |
Address area |
Address space per module |
without packing | 2 byte |
Digital outputs |
Number/binary outputs | 16 |
Load resistance range |
lower limit | 500 Ω |
upper limit | 2500 Ω |
Output current |
for signal "1" rated value | 16 mA |
Switching frequency |
with inductive load, max. | 20 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
up to 55 °C, max. | 330 mA; only up to 50 °C, limited by valves |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Parameter |
Remark | Diagnosis load voltage 2L+ |
Galvanic isolation |
between backplane bus and all other circuit components | Yes |
between the channels and backplane bus | Yes |
Galvanic isolation digital outputs |
between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
tested with |
Load voltage L+ against backplane bus | 500 V DC |
Dimensions |
Width | 120 mm |
Height | 152 mm |
Depth | 47 mm |
Status | Mar 12, 2012 |