SIMATIC S7-1200, ANALOG INPUT, SM 1231 TC, 8 AI THERMOCOUPLE

Артикул: 6ES7231-5QF30-0XB0
Наименование: SIMATIC S7-1200, ANALOG INPUT, SM 1231 TC, 8 AI THERMOCOUPLE (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC S7-1200, ANALOG INPUT, SM 1231 TC, 8 AI THERMOCOUPLE
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2011-03-31
Manuals weitere>>
Программируемый контроллер S7-1200   2009-12-16
SIMATIC S7-1200, ANALOG INPUT, SM 1231 TC, 8 AI THERMOCOUPLE
Supply voltage
24 V DC Yes
Input current
Current consumption, typ. 80 mA
from backplane bus 5 V DC, typ. 80 mA
Power losses
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 8; Thermocouples
permissible input frequency for current input (destruction limit), max. ± 35 V
Technical unit for temperature measurement adjustable Degrees Celsius/degrees Fahrenheit
Input ranges
Thermocouple Yes; J, K, T, E, R, S, N, C, TXK/XK(L); voltage range: +/-80 mV
Input ranges (rated values), voltages
-80 mV to +80 mV Yes
Input ranges (rated values), thermoelements
Type C Yes
Type E Yes
Type J Yes
Type K Yes
Type N Yes
Type R Yes
Type S Yes
Type T Yes
Type TXK/TXK(L) to GOST Yes
Thermocouple (TC)
permissible input voltage for voltage input (destruction limit), max. +-35V
Temperature compensation
Parameterizable No
Analog value creation
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 15 bit; + sign
Integration time, parameterizable No
Interference voltage suppression for interference frequency f1 in Hz 85 dB at 50 / 60 / 400 Hz
Analog value generation (in isochronous mode)
Smoothing of measured values
Parameterizable Yes
Errors/accuracies
cold connection point +/-1.5 °C
Temperature error (relative to input area) 25 °C ±0.1 % to 55 °C ±0.2 % total measurement range
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Common mode interference, min. 120 dB
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes; Can be read out
Monitoring the supply voltage Yes
Wire break Yes
Diagnostics indication LED
for status of the inputs Yes
for maintenance Yes
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 660 hPa
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 795 hPa
Pollutant concentrations
SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
C-TICK Yes
FM approval Yes
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weight
Weight, approx. 220 g
Status Mar 12, 2012