SM 332, 2 * 12 Bit, galv.-isol.

Артикул: 6ES7332-5HB81-0AB0
Наименование: SM 332, 2 * 12 Bit, galv.-isol. (siemens)
Производитель: Siemens


Наименование продукта
SM 332, 2 * 12 Bit, galv.-isol.
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1998-05-20 2003-08-13
SIMATIC S7-300, ANALOG OUTPUT SM 332, OPTICALLY ISOLATED, FOR EXPANDED TEMPERATURE RANGE 2 AO, U/I; 11/12 BITS RESOL., 20 PIN
Supply voltage
Load voltage L+
Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 240 mA
from backplane bus 5 V DC, max. 60 mA
Power losses
Power loss, typ. 3 W
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes
1 to 5 V Yes
-10 to +10 V Yes
Output ranges, current
0 to 20 mA Yes
-20 to +20 mA Yes
4 to 20 mA Yes
Load impedance (in rated range of output)
with voltage outputs, min. 1 kΩ
with voltage outputs, capacitive load, max. 1 µF
with current outputs, max. 500 Ω
with current outputs, inductive load, max. 10 mH
Cable length
Cable length, shielded, max. 200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 12 bit; +/-10 V, +/-20 mA, 4 to 20 mA, 1 to 5 V: 11 bits + sign; 0 to 10 V, 0 to 20 mA: 12 bits
Conversion time (per channel) 0.8 ms
Settling time
for resistive load 0.2 ms
for capacitive load 3.3 ms
for inductive load 0.5 ms
Errors/accuracies
Operational limit in overall temperature range
Voltage, relative to output area +/- 0,5 %
Current, relative to output area +/- 0,6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output area +/- 0,4 %
Current, relative to output area +/- 0,5 %
Interrupts/diagnostics/status information
Substitute values connectable Yes; Parameterizable
Alarms
Diagnostic alarm Yes
Diagnostic messages
Diagnostics Yes; Diagnostic information readable
Diagnostics indication LED
Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog outputs
between the channels and the backplane bus Yes
Isolation
Isolation checked with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weight
Weight, approx. 220 g