SIMATIC S7-400, DIGITAL OUTPUT MODULE, SM 422, ISOLATED, 16 DO, 20 - 125V DC, 1.5A WITH DIAGNOSTICS 8 POINT PER COMMON

Артикул: 6ES7422-5EH10-0AB0
Наименование: SIMATIC S7-400, DIGITAL OUTPUT MODULE, SM 422, ISOLATED, 16 DO, 20 - 125V DC, 1.5A WITH DIAGNOSTICS 8 POINT PER COMMON (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC S7-400, DIGITAL OUTPUT MODULE, SM 422, ISOLATED, 16 DO, 20 - 125V DC, 1.5A WITH DIAGNOSTICS 8 POINT PER COMMON
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1997-09-01 2003-10-01 2004-10-01 2014-10-01
Manuals weitere>>
Automation System S7-400 Module Specifications  2004-12-06
SIMATIC S7-400, DIGITAL OUTPUT MODULE, SM 422, ISOLATED, 16 DO, 20 - 125V DC, 1.5A WITH DIAGNOSTICS 8 POINT PER COMMON
Supply voltage
Load voltage L+
Rated values 20 to 125 V DC
permissible range, lower limit (DC) 20 V
permissible range, upper limit (DC) 138 V
Load voltage L1
Rated value (AC) 20 V; 20 to 138 V DC
Input current
from load voltage L+ (without load), max. 2 mA
from backplane bus 5 V DC, max. 700 mA
Power losses
Power loss, max. 10 W
Digital outputs
Number/binary outputs 16
Limitation of inductive shutdown voltage to -30 V
Lamp load, max. 8 W
Output voltage
for signal "1", min. L+ (-1 V)
Output current
for signal "1" rated value 1.5 A
for signal "1" permissible range for 0 to 60 °C, min. 5 mA
for signal "1" permissible range for 0 to 60 °C, max. 1.5 A
for signal "0" residual current, max. 0.5 mA
Switching frequency
with resistive load, max. 10 Hz
with inductive load, max. 0.1 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 60 °C, max. 8 A; 14 A with fan assembly
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes; Parameterizable
Diagnostic messages
Diagnostics Yes; internal/ external fault
Galvanic isolation
Galvanic isolation digital outputs
between the channels, in groups of 8
between the channels and the backplane bus Yes
Isolation
Isolation checked with 1500 V AC
Dimensions
Width 25 mm
Height 290 mm
Depth 210 mm
Weight
Weight, approx. 800 g
Status Mar 12, 2012

Назад в раздел