SIMATIC S7-400, FM 450-1 FUNCTION MODULE F. COUNT.FUNCT. WITH 2 CHANNELS INCL. CONFIG. PACKAGE ON CD

Артикул: 6ES7450-1AP00-0AE0
Наименование: SIMATIC S7-400, FM 450-1 FUNCTION MODULE F. COUNT.FUNCT. WITH 2 CHANNELS INCL. CONFIG. PACKAGE ON CD (siemens)
Производитель: Siemens


Наименование продукта
SIMATIC S7-400, FM 450-1 FUNCTION MODULE F. COUNT.FUNCT. WITH 2 CHANNELS INCL. CONFIG. PACKAGE ON CD
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-12-15
    Версия от 2012-02-25
 
SIMATIC S7-400, FM 450-1 FUNCTION MODULE F. COUNT.FUNCT. WITH 2 CHANNELS INCL. CONFIG. PACKAGE ON CD
Supply voltage
Load voltage 1L+
Reverse polarity protection Yes
Load voltage 2L+
Reverse polarity protection Yes
Aux. voltage 1L+, load voltage 2 L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V; Dynamic 18.5 V
permissible range, upper limit (DC) 28.8 V; dynamic 30.2 V
non-periodic skip
Duration 500 ms
Recovery time 50 s
Value 35 V
Input current
from load voltage 1L+ (without load), max. 40 mA
from backplane bus 5 V DC, max. 450 mA
Encoder supply
5 V encoder supply
5 V Yes; 5.2 V +/-2%
Short-circuit protection Yes
Output current, max. 300 mA
24 V encoder supply
24 V Yes; 1L+ (-3 V)
Short-circuit protection Yes
Output current, max. 300 mA
Power losses
Power loss, typ. 9 W
Digital inputs
Number/binary inputs 6
Functions 1 for gate start, 1 for gate stop, 1 for setting the counter
Input voltage
for signal "0" -28.8 to +5 V
for signal "1" +11 to +28.8 V
Input current
for signal "1", typ. 9 mA
Input delay (for rated value of input voltage)
Input frequency (with a time delay of 0.1 ms), max. 200 kHz
for standard inputs
Parameterizable Yes
at "0" to "1", max. 2.5 µs; >= 2.5 µs (200 kHz); <= 25 µs (20 kHz)
Digital outputs
Number/binary outputs 6
Functionality/short-circuit strength Yes; Clocked electronically
Limitation of inductive shutdown voltage to 2L+ (-39 V)
Output voltage
for signal "0", max. 3 V
for signal "1", min. 2L+ (-1.5 V)
Output current
for signal "1" rated value 0.5 A
for signal "1" permissible range for 0 to 60 °C, min. 5 mA
for signal "1" permissible range for 0 to 60 °C, max. 0.6 A
Output delay with resistive load
0 to "1", max. 300 µs
Encoder
Connectable encoders
Incremental encoder (symmetrical) Yes; With 2 pulse trains offset by 90°
Incremental encoder (asymmetrical) Yes
24 V initiator Yes
24 V directional element Yes; 1 pulse train, 1 direction level
Interrupts/diagnostics/status information
Status indicator Yes; 14 green LEDs for status of CR, DIR, inputs and outputs
Alarms
Diagnostic alarm Yes; Parameterizable
Hardware interrupt Yes; Parameterizable
Diagnostic messages
Diagnostic functions Yes
Diagnostics Yes; Diagnostic information readable
Diagnostics indication LED
Description 2 red LEDs for internal and external errors
Status indicator digital output (green) Yes
Status indicator digital input (green) Yes
Counter
Number of counter inputs 2; 32 bit or +/-31 bit
Counter input 5 V
Type RS 422
Terminating resistor 220 ?
Differential input voltage min. 0.5 V
Counting frequency, max. 500 kHz
Counter input 24 V
Input voltage, for signal "0" -30 to +5 V
Input voltage, for signal "1" +11 to +30 V
Input current, for signal "1", typ. 9 mA
Counting frequency, max. 200 kHz
Minimum pulse width >= 2.5 µs (200 kHz); <= 25 µs (20 kHz) (parameterizable)
Parameter
Remark Assigned binary addresses: 64 bytes/64 bytes
Galvanic isolation
Galvanic isolation digital inputs
between the channels and the backplane bus Yes; Optocoupler
Galvanic isolation digital outputs
between the channels and the backplane bus Yes; Optocoupler
Galvanic isolation counter
between the channels and the backplane bus Yes; Optocoupler
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V
Connection method
required front connector 1x 48-pin
Dimensions
Width 25 mm
Height 290 mm
Depth 210 mm
Weight
Weight, approx. 650 g
Status Feb 6, 2012