| SIMATIC WINAC RTX V4.1, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON CD, LICENSE KEY ON FD, CLASS B, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN 2000/XP AND VCI RTX, REFERENCE-HW: SIMATIC PC |
|
General information |
Firmware version | 4,1 |
Memory |
Work memory |
integrated | PC RAM can be used (non-paged memory) |
Load memory |
integrated RAM, max. | PC RAM can be used (non-paged memory) |
CPU processing times |
for bit operations, min. | 0.013 µs; typ. |
for fixed point arithmetic, min. | 0.025 µs; typ. |
for floating point arithmetic, min. | 0.025 µs; typ. |
Reference platform | Pentium IV, 2.4 GHz |
CPU-blocks |
DB |
Number, max. | Limited only by available PC work memory |
Size, max. | 64 kbyte |
FB |
Number, max. | Limited only by available PC work memory |
Size, max. | 64 kbyte |
FC |
Number, max. | Limited only by available PC work memory |
Size, max. | 64 kbyte |
OB |
Size, max. | 64 kbyte |
Number of time alarm OBs | 1 |
Number of delay alarm OBs | 1 |
Number of time interrupt OBs | 5 |
Number of process alarm OBs | 1 |
Nesting depth |
per priority class | 24 |
additional within an error OB | 24 |
Counters, timers and their retentivity |
S7 counter |
Number | 512 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 511 |
preset | 8 |
Counting range |
adjustable | Yes |
lower limit | 0 |
upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
S7 times |
Number | 512 |
Retentivity |
lower limit | 0 |
upper limit | 511 |
preset | 0 |
Time range |
lower limit | 10 ms |
upper limit | 9990 s |
IEC timer |
present | Yes |
Type | SFB |
Data areas and their retentivity |
Retentivity without UPS and PS Extension Board | none |
Retentivity with UPS | all data |
Flag |
Number, max. | 2 kbyte |
of which retentive | MB 0 to MB 2048 |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8 |
Address area |
I/O address area |
Inputs | 16 kbyte |
Outputs | 16 kbyte |
of which, distributed |
DP interface, inputs | 16 kbyte |
DP interface, outputs | 16 kbyte |
Process image |
Inputs, adjustable | 8 kbyte |
Outputs, adjustable | 8 kbyte |
Inputs, default | 512 byte |
Outputs, default | 512 byte |
Subprocess images |
Number of subprocess images, max. | 15 |
Digital channels |
Inputs | 131072 |
Outputs | 131072 |
Analog channels |
Inputs | 8192 |
Outputs | 8192 |
Hardware configuration |
Submodules |
Number of submodules, max | 4 |
of which PROFIBUS, max. | 4; CP 5613, CP 5613-A2 |
of which Industrial Ethernet, max. | 0 |
Number of operable FMs and CPs (recommended) |
FM | FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2 |
CP, point-to-point | CP 340, CP 341 distributed |
CP, LAN | Over PC CP |
Time of day |
Clock |
Hardware clock (real-time clock) | Yes |
battery-backed and synchronizable | Yes |
Clock synchronization |
supported | No |
2nd interface |
Type of interface | CP 5613, CP 5613-A2 |
Max. no. of simultaneously operable CPs | 4 |
Physics | RS 485 / PROFIBUS |
Isolated | Yes |
Functionality |
MPI | No |
DP master | Yes |
DP slave | No |
DP master |
Number of connections, max. | 50 |
Services |
PG/OP communication | Yes |
Routing | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | Yes |
Equidistance mode support | Yes |
SYNC/FREEZE | Yes |
Activation/deactivation of DP slaves | Yes |
Direct data exchange (slave-to-slave communication) | Yes |
DPV0 | Yes |
DPV1 | Yes |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 125 |
Address area |
Inputs, max. | 16 kbyte |
Outputs, max. | 16 kbyte |
User data per DP slave |
Inputs, max. |
|