Two-way Cartridge Cage Valves are intended for hydronic applications in a normal indoor environment to control flow of hot/chilled water glycol solution up to 60% concentration. These valves are designed for zone control of heating/cooling systems.
Features
Quick open, linear, and equal percentage flow characteristics available
Bi-directional installation
3000-series valves for floating and modulating non-fail safe applications
1000-series valves for two-position control
High close-off rating independent of Cv
Available with a variety of North American and international pipe fittings
No tools required for actuator installation or removal
Actuator removal does not require draining system
Service is by replacement of cartridge, not valve body
Cartridge replacement rebuilds valve to factory-new condition
Product Specifications
Maximum Safe Operating Pressure (psi)
300 psi
Maximum Safe Operating Pressure (kPa)
2068 kappa (20 Bar)
Includes
Cartridge installation wrench
Used With
VC actuators
Comments
internal thread
Approvals, Canadian Standards Association
CSA Certified
Timing
When used with VC series Actuator--On/Off models with 6 seconds, Floating and modulating with 2 min.
Ambient Temperature Range (F)
32 F to 150 F
Ambient Temperature Range (C)
0 C to 65 C
Body Pattern
Two-way, Straight-through
Pipe Size (inch)
1 in.
Pipe Size (DN)
DN25
Fluid Temperature (C)
1 C to 95 C
Fluid Temperature (F)
34 F to 203 F
Maximum Differential Pressure Ratings (Close-off) (psi)
60 psi
Maximum Differential Pressure Ratings (Close-off) (kPa)