AS-Interface safety module | VAA-2E2A-G2-S/EA2

Артикул: VAA-2E2A-G2-S/EA2
Наименование: AS-Interface safety module | VAA-2E2A-G2-S/EA2
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • Addressing jack
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring
  • Power supply of outputs from the external auxiliary voltage
  • 2 safe inputs for mechanical contacts such as EMERGENCY-STOP switch
  • Power supply of inputs from the module
  • Function display for bus, ext. auxiliary voltage, inputs and outputs
  • Output overload monitoring
  • Switchable internal logic operation of the inputs and outputs via parameter bit

Datasheet as PDF in following languages:


Technical Data: VAA-2E2A-G2-S/EA2

Product Description
G2 safety module
2 safety-related inputs and
2 conventional electronic outputs
General specifications
Slave typeSafety-Slave
AS-Interface specificationV2.1
Required master specification≥ V2.1
UL File NumberE87056
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
MTTFd200 a
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: Output supply overload
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 2 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 70 mA
Protection classIII
Input
Number/Type2 safety-related inputs for mechanical contacts, cross-circuit monitored:
2 single-channel contacts: up to category 2 in accordance with EN 954-1 or
1, 2-channel contact: up to category 4 in accordance with EN 954-1
Cable length must not exceed 30 m per input.
Supplyfrom AS-Interface
Voltage20 ... 30 V DC pulsed
Current loading capacityinput current limited ≤ 15 mA,
overload and short-circuit resistant
Output
Number/Type2 conventional electronic outputs, PNP
Supplyfrom external auxiliary voltage UAUX
Current1 A per output
Voltage≥ (UAUX - 0.5 V)
Programming instructions
ProfileS-7.B
IO code7
ID codeB
ID1 codeF
ID2 code0
Data bits (function via AS-Interface) input output
D0 dyn. safety code 1 OUT 1
D1 dyn. safety code 1 OUT 2
D2 dyn. safety code 2 -
D3 dyn. safety code 2 -
Parameter bits (programmable via AS-i)function
P0Logic operation:
P0 = 1 (Basic setting): The outputs are controlled via AS-Interface.
P0 = 0: The outputs are controlled via AS-Interface or the inputs. The corresponding output is activated on opening the contacts of an input.
P1not used
P2not used
P3not used
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 61326, EN 50295, EN 61496-1
Standard conformity
Electromagnetic compatibilityEN 61000-6-2, EN 61000-4-5 1 kV asymmetric, criterion B, EN 61000-6-4
Emitted interferenceEN 61000-6-4:2001
Insulation coordinationEN 50178:1998
Functional safetyEN 954-1:1996 (up to category 4), BIA Final Draft "Proposal for a principle to the verification and certification of field busses for transmission of safety related signals" 28.05.2000, IEC 61508 up to SIL3
Protection degreeEN 60529:2000
Fieldbus standardEN 50295:1999, IEC 62026-2:2006
Electrical safetyEN 50178:1998 , IEC 60204-1:2007
Ambient conditions
Ambient temperature-25 ... 55 В°C (-13 ... 131 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP67
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Material
HousingPBT
Mass100 g
MountingMounting base