Product Description |
G2 flat module 4 inputs (PNP) and 2 electronic outputs |
General specifications |
Slave type | A/B slave |
AS-Interface specification | V3.0 |
Required master specification | ≥ V2.1 |
Group, category, type of protection | II 3G EEx nA II T4 X II 3D Ex tD A22 IP67 T85В°C X |
Indicators/operating means |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs |
LED PWR | AS-Interface voltage; LED green |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
LED IN | switching state (input); 4 LED yellow |
LED OUT | Switching state (output); 2 LED yellow |
Electrical specifications |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V PELV from AS-Interface |
Rated operating current | ≤ 40 mA (without sensors) / max. 240 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 26 V |
Current loading capacity | ≤ 200 mA (TB ≤ 40 В°C), ≤ 150 mA (TB ≤ 60 В°C), overload-proof and short-circuit protected |
Input current | ≤ 8 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated) | ≤ 2 mA |
| 1 (attenuated) | ≥ 4 mA |
Output |
Number/Type | 2 electronic outputs, PNP, overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Current | 1 A per output, 2 A total |
Voltage | ≥ (UAUX - 0.5 V) |
Programming instructions |
Profile | S-7.A.2 |
IO code | 7 |
ID code | A |
ID1 code | 7 |
ID2 code | 2 |
Data bits (function via AS-Interface) | input output |
| D0 | IN1 OUT1 |
| D1 | IN2 OUT2 |
| D2 | IN3 - |
| D3 | IN4 - |
Parameter bits (programmable via AS-i) | function |
| P0 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Compliance with standards and directives |
Directive conformity | observe notices on the certificate of conformity. |
| EMC Directive 2004/108/EC | EN 50295:1999-10, EN 61326:2002-03
|
| ATEX Directive 94/9/EC | EN 60079-15:2003, IEC / EN 60947-5-2:2004 |
Standard conformity | |
| AS-Interface | EN 50295:1999, IEC 62026-2:2006 |
Ambient conditions |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Storage temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
Mechanical specifications |
Protection degree | IP67 according to EN 60529 |
Connection | AS-Interface/UAUX: Cable piercing method yellow flat cable/black flat cable or M12 round connector Inputs/outputs: M12 round connector |
Material | |
| Housing | PBT |
Cable | |
| Length | max. 30 m (Inputs) |
Mass | 150 g |
General information |
Use in the hazardous area | see instruction manuals |
| Category | 3G; 3D |